AC Cooling And Air Conditioning Systems Cumming, Georgia
Installed The Following Equipment
Upstairs System:
Installed A New Ducane Lynx, 3 TON, 17 SEER+, R-410a, Heat Pump And Air Handler For The Upstairs With A New 10 KW Heat Kit, Pad, Pan, Float Switch, Drain Line, Line Set, Return Plenum With A Filter Rack, Supply Plenum, All New R8 Flex, Boots And Grills, And 16
Cumming, GA
03-16-2022
AC Cooling And Air Conditioning Systems Cumming, Georgia
Uninstalled Existing Line Set, Drain Line, And Thermostat Wire For Upstairs System.
Installed A New Line Set, Drain Line, And Thermostat Wire (ran Down Interior Outside Wall).
Pressure Tested, Pulled Vacuum, And Recharged System.
Cumming, GA
10-30-2020
AC Cooling And Air Conditioning Systems Cumming, Georgia
Completed 1st Of 2 On 3 Systems.
Checked Units In Cooling Mode. Checked Electrical, Volts, Amps, Caps, And Charges. Cleaned Condenser Coils, Cleared Drain Lines, Treated Condensate Pumps, And Replaced Filters.
Main Unit-Added One Pound Of R-22 To Set Charge.
Kitchen Unit-Added One Pound Of R-410a To Set Charge. Also Replaced (2) AA Batteries For Kitchen Thermostat.
Units Are Cooling Properly At This Time.
Temperature Readings:
Main- Return 68.1*; Supply 49.1*
Kitchen- Return 68.5*; Supply 49.4*
Basement- Return 69.8*; Supply 50.5*
Cumming, GA
09-15-2020